design alternatives (page 7)
Notes
to the submission sheet on previous page:
- Retaining
wall to be constructed of Terraforce precast concrete blocks.
(Type as indicated)
- Blocks
placed as shown and to be filled with well tamped topsoil.
- For
walls retaining clay or shale, provide a free draining sand
layer behind wall. Backfill to be well rammed in 150mm layers.
- Drainage
outlet pipes to be provided at toe of slope to be capped
with geotextile.
- Stormwater
cut-off drain is to be provided above the wall where necessary.
- Ground
under all bases to be approved granular material well compacted
prior to constructing base.
- The
engineer is to be notified of any variations of levels or
dimensions shown.
- Minimum
concrete strength for concrete foundations to be 20MPa at
28 days. (to be designed accordingly)
- Shear
Keys with a minimum design shear stress of 0,3N/mm˛ are
to be installed as indicated.
i.e. 75 x 75 mm 1:4 cement or crusher-sand mortar or 40mm
H.D.P.E Class 6 pipe sections
- No
services or trenches permitted immediately in front of the
retaining wall.
- Maximum
superimposed loading as indicated behind Wall. (surcharge)
- Concrete
keys to be class 1 mortar or 15Mpa concrete.
- Please
refer to the Terraforce construction manual and the guide
to Terraforce L13 retaining walls for further detalls.
- The
Terraforce block retaining wall design spreadsheet can also
be used to assist in the design process.
|